 Powerstar UPS RT 15KVA RM 208V, 208V/120V 10KVA Step down
Transformer true online
|
UPS On-Line Powerstar 15 kva trueonline shipboard
rackmount UPS RT 15KVA RM 208V, 208V/120V 10KVA Step down Transformer
|
SURT15KRMXLT-1TF10K
Email Technical
Specifications Printer Friendly
|
|
More Images
|
Powerstar-UPS On-Line, 12 kW / 15 kVA, Input 208V /
Output 120V, 208V , Interface Port DB-9 RS-232, RJ-45 10/100 Base-T,
Smart-Slot , Extended runtime model , Rack Height 12 U
Includes: CD with software, Rack Mounting support rails,
Smart UPS signalling RS-232 cable, User Manual, Web/SNMP Management Card
|
|
|
|
Output Power Capacity
12 kW / 15 kVA
Max Configurable Power
12 kW / 15 kVA
Nominal Output Voltage
120V,208V
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
Efficiency at Full Load
94.0%
Output Voltage Distortion
Less than 5%
Output Frequency (sync to mains)
50/60 Hz +/- 3 Hz user adjustable +/- 0.1
Other Output Voltages
220,240
Crest Factor
3 : 1
Waveform Type
Sine wave
Output Connections
|
(1) Hard Wire 4-wire (2PH + N +G)
|
|
|
(2) NEMA L14-30R
|

|
|
(2) NEMA L5-20R
|

|
|
(4) NEMA L6-20R
|

|
|
(2) NEMA L6-30R
|

|
Overload Operat
Manual),Optional External Bypass
Input
Nominal Input Voltage
208V
Input Frequency
50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
|
Hard Wire 3-wire (2PH + G)
|
|
Input voltage range for main operations
160 - 280V
Other Input Voltages
240
Maximum Input Current
83A
Input Breaker Capacity
100.0 A
Input Total Harmonic Distortion
Less than 5% for full load
Batteries & Runtime
Battery Type
Maintenance-free sealed Lead-Acid battery with suspended
electrolyte : leakproof
Included Battery Modules
4
Typical recharge time
2.50 hour(s)
Replacement Battery
RBC44
RBC™ Quantity
4
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
End of Discharge Battery Voltage
+/-154 V
Efficiency in Battery Operation
93%
Curve fit to measured runtime data. All measurements taken
with new, fully charged batteries, at typical environmental conditions, with
no electrical input and balanced resistive load (PF = 1.0) output.
View Enlarged Graph
View Runtime Chart
Communications & Management
Interface Port(s)
DB-9 RS-232,RJ-45 10/100 Base-T,Smart-Slot
Pre-Installed SmartSlot™ Cards
AP9631
Control panel
Multi-function LCD status and control console
Audible Alarm
Audible and visible alarms : configurable delays
Emergency Power Off (EPO)
Yes
Surge Protection and Filtering
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge
let-through : zero clamping response time : meets UL 1449
Physical
Maximum Height
708.00 mm
Maximum Width
432.00 mm
Maximum Depth
773.00 mm
Rack Height
12U
Net Weight
347.73 KG
Shipping Weight
439.09 KG
Shipping Height
1396.00 mm
Shipping Width
610.00 mm
Shipping Depth
1003.00 mm
Color
Black
Units per Pallet
1.00
Environmental
Operating Environment
0 - 40 °C
Operating Relative Humidity
0 - 95%
Operating Elevation
0-3000 meters
Storage Temperature
-15 - 45 °C
Storage Relative Humidity
0 - 95%
Storage Elevation
0-15000 meters
Audible noise at 1 meter from surface of unit
50.00 dBA
Online Thermal Dissipation
2610.00 BTU/hr
Conformance
Regulatory Approvals
UL 1778
Standard Warranty
2 years repair or replace
**The time to recharge to 90% of full battery capacity
following a discharge to shutdown using a load rated for 1/2 the full load
rating of the UPS.
|