powerstar logo1.jpgPS6003rm3uxl 

Model no.  PS6003rm3uxl PS6003rm3u front.jpg

Line Interactive type UPS wired for Delta power

Dual pole circuit breakers

Auto Boost and Trim voltage trim without using

Inverter

Smart UPS tests itself and batteries periodically

Auto restart after a full run upon utility restoration

Cold Start capable

Hot swappable batteries

Output Power Capacity 2700 Watts / 3000 VA

Max Configurable Power2700 Watts / 3000 VA

Nominal Output Voltage 120V

Output Voltage Distortion Less than 5% at full load

Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal, 57 - 63 Hz for 60 Hz nominal

Crest Factor up to 5: 1

Waveform Type Sine wave

Output Connections (standard)

(9) NEMA 5-15R

http://www.apc.com/resource/images/conn_5-15R_sm.gif

(2) NEMA 5-20R

http://www.apc.com/resource/images/conn_5-20R_sm.gif

Output Connections -optional    L5-30R (contact us for other connections)

Input

Nominal Input Voltage 120V

Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)

Input Connections NEMA L5-30P

http://www.apc.com/resource/images/conn_L5-30P_sm.gif

Cord Length 8 feet (2.44 meters)

Input voltage range for main operations 82 - 144V

Input voltage adjustable range for mains operation 75 - 154V

Transfer Time 2-4 ms

Batteries & Runtime

Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leakproof

Typical recharge time 3 hour(s)

Replacement Battery PSRBC105 (high temperature long life batteries available for this unit)

PSRBC Quantity 1

Typical Backup Time at Half Load 15.0 minutes (1350 Watts)

Typical Backup Time at Full Load 5.4 minutes (2700 Watts)

Typical Backup Time at 900 Watts= 31 minutes


 

Runtime with 1 additional 3u battery pack 26”deep (159 lb) PS6003-3uBP

Typical Backup Time at Half Load 63 minutes (1350 Watts)

Typical Backup Time at Full Load 21 minutes (2700 Watts)

Typical Backup Time at 900 Watts= 106 minutes

Typical Backup Time =30 minutes @2100 Watts

 

Interface Port(s)

DB-9 RS-232,SmartSlot

Available SmartSlot™ Interface Quantity -1 (for SNMP Network card PS9617)

 

Control panel

LED status display with load and battery bar-graphs and On Line: On Battery: Replace Battery: and Overload Indicators

Audible Alarm -Alarm when on battery: distinctive low battery alarm: configurable delays

Emergency Power Off (EPO)- Optional

 

Protection

Surge energy rating 880 Joules

Filtering- Full time multi-pole noise filtering: 0.3% IEEE surge let-through: zero clamping response time: meets UL 1449

 

Dimensions

Maximum Height 5.25 inches (133 mm)

Maximum Width 19.00 inches (483 mm)

Maximum Depth 26.00 inches (660 mm)

Rack Height 3U

Net Weight 131.00 lbs. (59.55 kg)

Shipping Weight 153.00 lbs. (69.55 kg)

Shipping Height 12.00 inches (305 mm)

Shipping Width 24.00 inches (610 mm)

Shipping Depth 32.00 inches (813 mm)

Color Black

Mounting rails included for rack mounting

 

Operating Environment

32 - 104 °F (0 - 40 °C)  (battery dependant)

Operating Relative Humidity 0 - 95%

Operating Elevation 0-10000 feet (0-3000 meters)

Storage Temperature 5 - 113 °F (-15 - 45 °C)

Storage Relative Humidity 0 - 95%

Storage Elevation 0-50000 feet (0-15000 meters)

Audible noise at 1 meter from surface of unit 53.00 dBA

Online Thermal Dissipation-375 BTU /hr

 

2 year warranty on parts and Labor